The ideal place to outsource your infrastructures, on the outskirts of Paris
Aurora in a few numvers
-
Site IT capacity: 100 kW (2 lanes)
-
Installed cooling capacity: 246 kWf (2N+)
-
Volume open to sharing: 56 bays (47U)
-
24/7 autonomous access.
Electricity
-
Nominal source consisting of an ENEDIS 250 kVA substation;
-
The site has our own isolation transformer;
-
Distribution of the source on 2 autonomous electrical channels supplying each equipment independently.
-
Intermediate back-up provided by Eaton 93PM (200 kW) inverters and lithium-ion batteries.
-
Relief provided by SDMO 250 kW generators with individual tanks.
Air conditioning
-
Stulz equipment in 2N training (main model: ASD 772 AS);
-
Direct expansion system using refrigerant gas type R410A;
-
Refrigerated air circulation in false floors and ducted return in hot aisles;
-
A temperature of 20° is thus maintained in cold corridors.
Security and access control
-
Each access by name is time-stamped;
-
Every move is traceable in the information system in accordance with ISO27001;
-
Access control by means of individual digicodes, magnetic badges and verification of identity documents;
-
CCTV and intrusion sensors.
Fire safety
-
Firewalls 1 hour;
-
Detection in IT rooms by means of VESDA-type smoke extraction systems;
-
Complementary detection in ambience and technical floor in double criteria by smoke and flame detectors;
-
Automatic shutdown in critical rooms using internal non-chemical gas;
-
APSAD R7 compliant installation.
PUE and energy savings
Available services
-
Colocation: Single, 1/4, 1/2 rack or 1 rack
-
Proximity gestures
-
Network: Transit Aqua Ray up to 10G (or own site on request)
Visit by appointment